The 1663, one of our multifunction testers, tests to all local regulations & provides test results for complete documentation. Learn more today!
Key Features
- Tests continuity at L-N, N-PE inputs
- Tests smooth dc sensitive RCDs (Type B)
- Tests earth resistance, voltage, and frequency
- Offers multiple test voltages: 50 V, 100 V, 250 V, 500 V, 1000 V
- 6 mA RDC-DD testing for EV charging stations
The Fluke 1663 SCH Installation Tester with RCD Type B Schuko # FLK-1663 SCH is manufactured by Fluke. Valley Instrument Service is an authorized Fluke dealer offering full sales support, NIST-traceable calibration, and expert technical assistance.
Have questions about this product?
Our team can help with product selection, specs, pricing, and application support.
Contact Us or Call (661) 327-8681| Range | 500 V |
| Resolution | 0.1 V |
| Accuracy 45 Hz – 66 Hz | 0.8% + 3 |
| Input impedance | 360 kΩ |
| Overload protection | 660 V rms |
| Range (autoranging) | 20 Ω / 200 Ω / 2000 Ω |
| Open Circuit Voltage | >4 V |
| Test voltages | 50-100-250-500-1000 V |
| Accuracy of test voltage (at rated test current) | +10%, -0% |
| Test voltage | 50 V100 V250 V500 V1000 V |
| Insulation resistance range | 20 MΩ / 50 MΩ20 MΩ / 100 MΩ20 MΩ / 200 MΩ20 MΩ / 200 MΩ / 500 MΩ20 MΩ / 200 MΩ / 1000 MΩ |
| Test current | 1 mA @ 50 kΩ1 mA @ 100 kΩ1 mA @ 250 kΩ1 mA @ 500 kΩ1 mA @ 1 MΩ |
| Computation | Prospective earth fault current (PEFC) or Prospective short circuit current (PSC) determined by dividing measured mains voltage by measured loop (L-PE) resistance or line (L-N) resistance, respectively. |
| RCD Type | AC¹G²,S³ |
| Model 1663 | A4, AC¹, G²,S³ |
| Model 1664 FC | A, AC, B5, S |
| Notes | ¹Responds to AC²General, no delay³Time delay⁴Responds to pulsed signal⁵Responds to smooth DC signal |
| Current settings¹ | 10-30-100-300-500-1000 mA – VAR10-30-100 mA |
| Multiplier | x ½, x 1x 5VAR Mode Type B - 6, 60, 200 mA |
| RCD Type G | 310 ms50 ms |
| RCD Type S | 510 ms160 ms |
| EV / RDC-DD | 6 mA - 10s60 mA - 0.3s200 mA - 0.1s |
| Current range | 30% to 110% of RCD rated current¹<2 mA to 6 mA smooth DC³ |
| Step size | 10% of IΔN²Linear rising within 30 s |
| Measurement accuracy | ±5% |
| Specified trip current ranges (EN 61008-1) | 50% to 100% for Type AC35% to 140% for Type A (>10 mA)35% to 200% for Type A (≤10 mA)50% to 200% for Type B |
| Frequency | 128 Hz |
| Output Voltage | 25 V |
| Icon | Phase Sequence indicator is active. |
| Size (L x W x H) | 10 x 25 x 12.5 cm |
| Weight (incl. batteries) | 1.3 Kg |
| Battery size, quantity | Type AA, 6 ea. |
| Sealing | IP-40 |
| Safety | Complies with EN/IEC 61010-1 and EN/IEC 61010-2-034 |
| Overvoltage | CAT III / 500V; CAT IV 300V |
| Performance | EN61557-1 to EN61557-7 and EN61557-10 |
This product is part of a family with 2 models. Select a model below to view details.
| Model | Price | |
|---|---|---|
FLK-1663 US | $2,407.99 | View Details → |
FLK-1663 SCHCurrent | $2,312.99 | Viewing |
Related Products

1662 SCH Installation Tester with Mem Schuko
Installation Tester with Mem Schuko
166X Main Test Cord, North America
Replacement main test cord for Fluke 1660 series multifunction installation testers. North America version.

1672 Installation Tester with TruTest Software (Schuko)
Multifunction installation tester with TruTest reporting software. Insulation resistance, loop/line resistance, voltage, frequency, and polarity testing. Schuko (CEE 7/7) plug.

1673FC Installation Tester with Fluke Connect & TruTest Software (Schuko)
Multifunction installation tester with Fluke Connect wireless and TruTest reporting software. Insulation resistance, earth ground, loop/line resistance, voltage, frequency, and polarity. Schuko (CEE 7/7) plug.